.01 General
Exit lights shall
be greenbe green LED and have stencil face
with greenwith green letters. In small renovation projects, red LED may be used to match existing signs. In architecturally-sensitive applications: use edge-lit type such as Lithonia LRP.
Flush mount types are desirable because they are more vandal-proof. Consider vandal-resistant models for dormitory design.
Self-contained exit signs powered by a radioactive source (tritium or similar) and photoluminescent exit signs are not acceptable.
Equipment shall be UL924 listed and labeled.