.01 General
  1. Exit lights shall be green LED and have stencil face with green letters.  In small renovation projects, red LED may be used to match existing signs. In architecturally-sensitive applications: use edge-lit type such as Lithonia LRP.
  2. Flush mount types are desirable because they are more vandal-proof.  Consider vandal-resistant models for dormitory design.
  3. Self-contained exit signs powered by a radioactive source (tritium or similar) and photoluminescent exit signs are not acceptable.
  4. Equipment shall be UL924 listed and labeled.