The use of other types of fire-extinguishing systems shall be discussed with the University.
Water Spray Fixed Systems shall conform to NFPA 15 and FM Global Data Sheets 4-1N.
Dry Chemical Extinguishing Systems shall conform to NFPA 17 and FM Global Data Sheets 4-10.
Wet Chemical Extinguishing Systems shall conform to NFPA 17A.
21 21 00 CARBON-DIOXIDE FIRE-EXTINGUISHING SYSTEMS
.01 Carbon Dioxide Fire-Extinguishing Systems
21 24 00 DRY-CHEMICAL FIRE-EXTINGUISHING SYSTEMS
.01 Halon Fire-Extinguishing Systems
Conform to NFPA 12A.
Contact the University for required Halon system reserve, tests required, and FM Global approvals of design. Tests shall be conducted during unoccupied periods. Tests shall be witnessed by OPP, FM Global, and EH&S and be scheduled two weeks in advance.