HumidifiersApplication:
- The steam source must be from building steam whenever possible.
- Electronic steam generators to be used only when building steam is not available.
- Water softening equipment shall be provided when electronic steam generators are used.
- Provide two changes of canisters.
- Follow manufacturers' guidelines for location.
- Provide access panel with a glass vision panel on downstream side of manifold.
- Controls (See 23 09 00).
- Refer to Detail [23 xx xx .xx]. Details are not yet available in WEB-based manual.
.02 Dehumidifiers
- Small packaged dehumidifiers shall be arranged so condensate is piped to sanitary system.