Humidifiers
Application:
  1. The steam source must be from building steam whenever possible.
    1. Electronic steam generators to be used only when building steam is not available.
    2. Water softening equipment shall be provided when electronic steam generators are used.
    3. Provide two changes of canisters.
  2. Follow manufacturers' guidelines for location.
  3. Provide access panel with a glass vision panel on downstream side of manifold.
  4. Controls (See 23 09 00).
  5. Refer to Detail [23 xx xx .xx].  Details are not yet available in WEB-based manual. 

.02 Dehumidifiers
  1. Small packaged dehumidifiers shall be arranged so condensate is piped to sanitary system.