23 84 00 HUMIDITY CONTROL EQUIPMENT

23 84 00 HUMIDITY CONTROL EQUIPMENT

.01 Design Requirements

  1. Application

    1. Section 23 84 00 of this Standard is intended to cover special circumstances where the occupancy or a process requires humidification or dehumidification outside of the default indoor design criteria defined in Section 23 00 00. 

    2. Centralized or terminal humidification shall not be provided for ordinary space conditioning purposes.

      1. For reference to designer: Humidification systems have the potential to cause considerable damage to building envelopes and contribute to indoor air quality issues. OPP requires specific documentation and approvals to avoid the mis-application of these systems. The successful implementation of a humidification system requires a firm understanding of the environmental requirements, operational capabilities of the equipment, and coordination with other building systems.

    3. Humidification is only permissible to maintain specific environmental conditions for a special equipment or process. These special purposes shall be identified by the Designer during the schematic design phase and are subject to review and approval by OPP.

      1. The Designer shall document on the design drawings the required temperature/humidity ranges, operational tolerances, and location of all humidified spaces/equipment.

  2. Allocation

    1. To preserve the integrity of building enclosures and avoid interior condensation, the Designer shall prioritize allocating humidified spaces to locations without exterior exposure.

    2. Where exterior exposure in humidified spaces is unavoidable the Designer shall perform the following building envelope analysis, which is subject to review and approval by OPP.

      1. Calculate the surface temperatures of all components in a wall/roof/floor assembly at Design winter conditions.

      2. Establish the indoor air dewpoint range according to the required temperature and humidity targets.

      3. If condensation were to occur, identify the risks to the occupancy and/or process.

      4. Evaluate the effects of moisture migration through the building envelope materials

    3. Humidified spaces shall be provided with continuous vapor barrier to manage moisture migration between adjacent spaces with different levels of humidification.

  3. System Selection

    1. Designer shall calculate humidification and dehumidification loads based on indoor design requirements, climatic conditions, and moisture gain due to internal loads, infiltration, and envelope moisture migration. Calculations shall be submitted to OPP for review and approval.

    2. Humidification:

      1. All humidification loads shall be calculated based on ASHRAE Climatic Design Information for the “99.6% Heating DB” condition.

    3. Dehumidification:

      1. All dehumidification loads shall be calculated based on ASHRAE Climatic Design Information for the “0.4% Dehumidification” condition.

      2. Refer to Table 238400.01 - Dehumidification system selection matrix

  4. Recognized industry resources

    1. The following chapters from the ASHRAE HVAC Systems and Equipment Handbook:

      1. Humidifiers

      2. Air-Cooling and Dehumidifying Coils

      3. Desiccant Dehumidification and Pressure-Drying Equipment

      4. Mechanical Dehumidifiers and Related Components

    2. The Dehumidification Handbook – Third Edition (Munters)

    3. Whole Building Design Guide (https://www.wbdg.org/)

      1. Building Envelope Design Guide

.02 Humidifiers

  1. Heating source selection:

    1. Natural gas is the preferred heating source for humidification systems.

    2. Where natural gas is unavailable, electricity is the second preference.

    3. The use of campus steam is not preferrable in either direct-injection humidifiers or indirect steam generators. All proposed uses of campus- or building-generated steam for humidification shall be reviewed and approved with OPP.

      1. For reference to Designer: The University is transitioning away from steam as a distributed heating source. The eventual process of converting all building systems to non-steam heating sources is made easier with proactive, strategic equipment selection.

  2. Humidifier types:

    1. Heated pan, centrifugal, ultrasonic, and wetted-media type humidifiers are prohibited.

    2. All isothermal humidifiers require insulated dispersion tubes. This insulation shall be factory applied, non-fibrous/closed-cell, UV light resistant, and have a minimum R-value of 0.5. Steam-jacketed manifolds are prohibited due to the operational limitations from the associated sensible heat gain.

    3. Atomizing humidifiers

      1. Pressurized water-humidifiers are the only permissible type of atomizing humidifier.

      2. Atomizing humidifiers shall not be used for terminal humidification.

      3. For reference to Designer: Adiabatic-type humidifiers (atomizing) require additional heating coil capacity to compensate for the drop in air temperature associated with the heat of vaporization. This can limit the operational flexibility of air systems. The applicability of isothermal versus adiabatic humidifiers shall be reviewed on a case-by-case basis.

    4. Direct steam injection humidifiers

      1. Direct injection humidifiers shall be provided with a motorized isolation valve and a modulating steam control valve.

    5. Self-contained humidifiers

      1. Self-contained (indirect) humidifiers shall utilize building steam or natural gas as the energy source where available.

      2. Resistive electric type shall be used for most applications where the energy source is electric.

      3. Immersed electrode canister type shall be used for non-critical or temporary applications only.

  3. All humidifiers requiring make-up water shall be provided with water treatment systems – no exceptions.

    1. Humidifiers fed from water softeners shall be provided with an automatic flushing and dilution cycle.

    2. Humidifier equipment and piping fed with demineralized water (RO/DI) must withstand the corrosive effects of this water.

  4. Humidifier installation requirements:

    1. Follow manufacturer’s guidelines for locating duct mounted distribution manifolds.

    2. Provide duct access door with a glass vision panel on downstream side of duct mounted manifolds.

    3. Duct mounted humidifiers shall be installed in a section of welded 304 stainless steel ductwork with a minimum length resulting from 1 foot upstream plus three times the absorption distance downstream of the humidifier. This humidifier section shall have a double-sloped bottom with drain connection.

.03 Dehumidifiers

  1. Cooling/dehumidification source selection:

    1. The campus chilled water utility or a pre-existing building chilled water source shall be used for dehumidification to the greatest extent possible.

    2. Where existing chilled water sources are unavailable/insufficient for dehumidification, DX cooling systems are the next preferred source.

      1. For reference to Designer: This preference for DX-based systems is mostly due to their relative simplicity in comparison to operating a stand-alone chiller.

    3. Desiccant-based dehumidification systems shall be used where:

      1. Very low humidity levels are required (see table below) or,

      2. in high latent cooling applications where a desiccant-based system would be significantly more energy efficient than cooling-based dehumidification.

    4. The least preferred dehumidification method is low-temperature chilled water/glycol (<42F EWT), which should be reserved for critical applications with high stability requirements. These systems are not favorable given the cost and complexity of operating a dedicated chiller and hydronic loop.

    5. Small packaged heat pump dehumidifiers are typically limited to temporary, portable systems and are not intended for permanent installation. If used, these units shall be arranged so condensate is piped to the sanitary system.

Table 238400.01 - Dehumidification system selection matrix

Table 238400.01 - Dehumidification system selection matrix

System Type

Practical Space

Temperature/RH Limit

Notes

Hydronic cooling coils with direct

or indirect connections to campus

CHW (with reheat)

75F/60% RH

Select cooling coils for 43F EWT for normal comfort dehumidification applications and 45F EWT for special applications.

Glycol Chiller (with reheat)

70F/45% RH

Requires separate remote chiller.

DX Cooling (with reheat)

70F/45% RH

 

Desiccant-based

50F/35% RH

 

 

 

Page Navigation


Related Files

  File Modified