23 50 00 CENTRAL HEATING EQUIPMENT

23 50 00 CENTRAL HEATING EQUIPMENT

.01 Combustion Safeguards
  1. All fuel burner combustion safeguards on gas-fired boilers over 100 HP and oil-fired boilers over 50 HP should be Factory Mutual approved equipment.
  2. Drawings, including section details of wiring and gas train, along with a Factory Mutual Application for acceptance form, shall be submitted to Factory Mutual for review and acceptance prior to installation.
  3. Final approval is based on a satisfactory field test of completed installation.
  4. Gas fired unit heaters up to 400,000 BTUs need AGA approval. 