.01 Finish Hardware Requirements

    1. Office Doors:
      1. Locks shall be one of the following:
        1. Sargent #8205 WTJ.
        2. Best 45H7A3J
        3. Schlage L9050 03L
        Latch bolt operated by lever either side except when outside lever is locked by button or toggle in faceplate; latch is retracted by key outside. Auxiliary bolt deadlatch.
      2. No door closers unless required by current applicable codes. 
        Office suites main entrance door may use cast iron or aluminum body closer if requested by occupants.
    2. Classroom Doors:
      1. Locks shall be one of the following:
        1. Sargent 8237 WTJ
        2. Best 45H7R3J
        3. Schlage L9070 03L
        Classroom function, key outside locks or unlocks outer lever; Interior lever always free. 
      1. Door closers shall be one of the following:
        1. Cast iron body (preferred): Lecture Halls (more than 75 occupants)
          1. LCN 4010/4111
          2. Stanley QDC115
          3. Sargent 281
        2. Cast aluminum (extra heavy duty) body may be used for classrooms 49-75 occupants:
          1. Stanley CLD-4551
          2. Sargent 351
          3. Norton 7500
        3. Cast aluminum (heavy duty) body may be used for classrooms under 50 occupants:
          1. Stanley CLD-3500
          2. Sargent 1430
          3. Norton 8500
          4. LCN 1450
      2. Inactive leaf of double doors shall have mortise flush bolts head and foot
        1. Rockwood 555
        2. Trimco 3915
        3. Ives 457
      3. See Division 13 20 10 for further references to the General Purpose Classroom document that includes information on doors and hardware.
    1. Laboratory Doors:
      1. Locksets and trim shall be one of the following:
        1. Sargent #8225 WTJ.
        2. Best 45H7T3J
        3. Schlage L9453 03L
        Latch bolt by lever either side. Dead bolt by key outside and turnpiece inside. Projecting deadbolt locks outside lever. Turning inside lever retracts both latchbolt and deadbolt simultaneously, unlocking outside lever.
      2. Door closers shall be one of the following:
        1. Cast iron body (preferred):
          1. LCN 4010/4111
          2. Stanley QDC115
          3. Sargent 281
        2. Cast aluminum (extra heavy duty) body may be used for undergraduate labs:
          1. Stanley CLD-4500
          2. Sargent 351
          3. Norton 7500
        3. Cast aluminum (heavy duty) body may be used for graduate labs:
          1. Stanley CLD-3500
          2. Sargent 1430
          3. Norton 8500
          4. LCN 1450
      3. Inactive leaf of double doors shall have mortise flush bolts head and foot
        1. Rockwood 555
        2. Trimco 3915
        3. Ives 457
    2. Storage Room Doors:
      1. Locks shall be one of the following:
        1. Sargent 8204 WTJ
        2. Best 45H7D3J
        3. Schlage L9080 03L
        Storeroom function, key retracts latchbolt but always remains locked; Interior lever always free.
      2. No door closers unless required by current applicable codes or facility programming requirements.
    3. Janitor Closet, Janitor Storage, and Utility Room Doors:
      1. Locks shall be one of the following:
        1. Sargent 8204 WTJ
        2. Best 45H4D3J
        3. Schlage L9080 03L
        Storeroom function, key retracts latchbolt but always remains locked; Interior lever always free.
      1. No door closers unless required by current applicable codes or facility programming requirements.
    1. Public Toilet Doors:
      1. At public restrooms with multiple stalls, doors shall be equipped with stainless steel push/pulls:
        1. Rockwood BF110 x 70C
        2. Ives 8302-10
        3. Trimco 1018-3B with matching push plates, minimum 18 ga, sized 8" x 16"
      2. Door closers shall be one of the following:
        1. Cast iron body (preferred):
          1. LCN 4010/4111
          2. Stanley QDC100
          3. Sargent 281
        2. Cast aluminum (extra heavy duty) may be used for single user toilet rooms:
          1. Stanley CLD-4500
          2. Sargent 351
          3. Norton 7500
      3. Provide kickdown holder where current applicable code permits:
        1. Rockwood 461
        2. Ives FS452
        3. Trimco 1220
    2. Communicating Doors:
      1. Locks shall be one of the following:
        1. Sargent 8226 WTJ
        2. Best 45H7G3J
        3. Schlage L9466 03L
        Latch bolt by either side. Deadbolt by key either side. Levers and deadbolt work independently. Code requires alternate exit in rooms with this lock function to avoid lock-in. 
      1. No door closer, unless required by current applicable code.
    1. Stair Tower Doors:
      1. Exit devices and trim for single doors shall be one of the following:
        1. Von Duprin #98L-F-BE x 996L-R-03
        2. Precision FL-2114 x 4914C
        3. Sargent 8815 x 715ETJ
        Finish shall be US32D
      2. Exit devices and trim for paired doors shall be one of the following:
        1. Von Duprin #9827L-BE-LBR x 996L-R-03
        2. Precision FL-2114LBR x 4914C
        3. Sargent NB8715 x 715ETJ
        4. Finish shall be US32D
          No bottom latch or rod; Provide standard fire bolt to be installed 12" up from bottom of doors between pairs.
    1. OPERATION: exit by push bar, always free; entry by lever, always free
    2. Door closers shall be one of the following:
      1. LCN 4010/4111
      2. Stanley QDC100
      3. Sargent 281
      Bodies shall be cast iron, cast aluminum bodies are not acceptable.
    3. Hold open arms are not allowed on fire rated door. If hold-open function is desired, wall mounted magnetic holder tired into the fire alarms system shall be used:
      1. Rixson 997
      2. LCN SEM7840
      3. ABH 2100
  1. A. Exterior Aluminum Doors (narrow lock stile):
    1. Exit devices for single doors shall be one of the following:
      1. Von Duprin 33NL x 3982-6
      2. Precision 2403 x Rockwood BF158
      3. Sargent AD8405 x 862
      Finish shall be US32D
    2. At paired doors, use exit devices as listed above in conjunction with removable mullion:
      1. Von Duprin 4954
      2. Precision 822
      3. Sargent 980
    3. Prefer to not use surface vertical rod devices at exterior pairs, unless absolutely required for usage (if used, vertical rod extended latch guard is required). Do not use concealed vertical rod exit devices in any application.
    4. Operation: Egress by inside push bar, always free. Entry by key or card reader, which would retract latch and allows door to be pulled open. Do not provide cylinder dogging (unless facility security programming allows) to allow for push-pull operation.
    5. Door closers shall be one of the following:
      1. LCN 4010/4111
      2. Stanley QDC100
      3. Sargent 281
      Bodies shall be cast iron, cast aluminum bodies are not acceptable. Provide drop plates and fin stop spacers as required for correct installation on narrow top rail.
    1. B. Exterior Hollow Metal Doors (wide lock stile)
      1. Exit devices for single door shall be one of the following:
        1. Von Duprin 99NL x 392-6
        2. Precision 2103 x Rockwood BF158
        3. Sargent 8805 x 862
        4. Finish shall be US32D.
      2. At paired door, use exit devices as listed above in conjunction with removable mullion:
        1. Von Duprin 4954
        2. Precision 822
        3. Sargent 980
      3. Prefer to not use surface vertical rod devices at exterior pairs, unless absolutely required for usage (if used, vertical rod extended latch guard is required). Do not use concealed vertical rod exit devices in any application.
      4. Operation: Egress by inside push bar, always free. Entry by key or card reader, which retracts latch and allows door to be pulled open. Do not provide cylinder dogging (unless facility security programming allows) to allow for push-pull operation.
      5. Door closers shall be one of the following:
        1. LCN 4010/4111
        2. Stanley QDC100
        3. Sargent 281
        Bodies shall be cast iron, cast aluminum bodies are not acceptable.
    2. Vestibule Doors:
      1. Each door will have dummy push-pull bar to match exterior:
        1. Von Duprin 330 x 392-6
        2. Precision 671 DR x Rockwood BF158
        3. Sargent 8893 x 862
        Finish shall be US32D
      2. Door closers shall be one of the following:
        1. LCN 4010/4111
        2. Stanley QDC100
        3. Sargent 281
        Bodies shall be cast iron, cast aluminum bodies are not acceptable.
      NOTE: select exterior opening applications may warrant an in-ground closer. In-ground Rixson closers maybe used where doors are located under covered entrances away from the elements, subject to review from OPP. Vestibule and interior applications may use in-ground Rixson closers. Model shall be heavy duty, and specific to door characteristics and/or other facility requirements.
  1. Low Energy Power Openers (section 08 71 13 included for quick reference)
    1. Norton 6000 series
    2. LCN 4600 series
    3. Finish shall compliment the opening's frame and/or closers in the surrounding area.
    4. Actuator shall be by the above manufacturers or Larco.
      1. wireless actuators shall only be used on interior applications
      Closer bodies shall be cast iron, cast aluminum bodies are not acceptable.
    5. Bollards shall be minimum 42-inches high by 5-inches square and able to accept the push plate actuator, card reader and proximity reader. Color to be approved by Office of Physical Plant (OPP) before project bid phase.
    6. Note: Advances in technology are permitted where power opener product will provide substantially equivalent or greater access/ease of use. Submit product to OPP for consideration.
  2. Residence Hall Bedroom Doors:
    1. Locksets shall be one of the following:
      1. Sargent 8225 WTJ
      2. Best 45H7T3J
      3. Schlage L9453 03L
      Latch bolt by either side. Deadbolt by key or card reader outside and turn piece inside. Projecting deadbolt locks outside lever. Turning inside lever retracts both latch bolt and deadbolt simultaneously, unlocking outside lever.
    2. Door closers shall be one of the following:
      1. Cast iron body (preferred):
        1. LCN 4010/4111
        2. Stanley QDC100
        3. Sargent 281
      2. Cast aluminum (extra heavy duty) may be used:
        1. Stanley CLD-4500
        2. Sargent 351
        3. Norton 7500
    3. Kickplates and mop plates shall be 18 ga stainless steel with beveled edges.
  3. Uncontrolled Exit Doors:
    1. All doors shall be equipped with proper exterior door hardware as listed above with an emergency exit alarm:
      1. Detex EAX-500
      2. Alarm Lock PG21
    2. Emergency exit alarms will be armed with a small-format cylinder installed in alarm case. Where required for usage, also provide exterior rim cylinder to allow for arming/disarming alarm from outside.
    3. Exit alarms are battery operated (where applicable with prior approval).
  4. Lock Cylinders:
    1. All lock cylinders shall be 7-pin small-format type removable core.
    2. Keying / supply options:
      1. Specifications which require factory keying, provide Best core 1C72, No Substitutions.
      2. Specifications which list keying by the University Lock Shop, provide the following uncombinated or 0-bitted small format cores:
        1. Best 1C72 (no substitution)
        Import or other-brand cores will not be considered. Provide 2 key blanks with every core for Lock Shop use.
    3. Factory keying: All keys shall be embossed with the letters "PSU" and stamped 'DO NOT DUPLICATE' and key symbol as directed by the University.
    4. The contractor shall use construction cores furnished by the lock supplier and will return same after permanent cores are installed
    5. All key-operated elevator switches will be provided with small format cylinders to match key system.
    6. All small-format cylinders and cores will be furnished under the Finish Hardware Section.
  5. Electric strikes
    1. HES: Cylindrical/Mortise locks 1006
      1. Rim exit devices 9600
    2. Von Duprin: Cylindrical/Mortise locks 6200 series
      1. Rim exit devices EN800 series
    3. Trine: Cylindrical/Mortise locks EN400 series
      1. Rim exit devices EN800 series
  6. Hinges:
    1. All doors shall be equipped with proper size, type and number of hinges. Provide non-removable pins at exterior doors and interior secure doors swinging out.
    2. Interior doors up to 36" wide shall be provided with one of the following:
      1. Stanley FBB179
      2. McKinney TA2714
      3. Ives 5BB1
    3. Interior doors over 36" wide shall be provided with one of the following:
      1. Stanley FBB168
      2. McKinney T4A3786
      3. Ives 5BB1HW
      4. (extra heavy weight)
    4. Exterior doors shall be provided with one of the following:
      1. Stanley FBB199
      2. McKinney T4A3386
      3. Ives 5BB1HWSS
      4. (stainless steel extra heavy weight).
      All exterior hinges to be NRP.
    5. Continuous Hinges maybe used in lieu of "butt" hinges where the application would warrant enhanced durability /aesthetics.
      1. Stanley 661 HD
      2. Pemko CFM83 SLF HD
      3. Ives 112 HD

  7. Door Stops, Holder and Bumpers:
    1. Doors that open to a perpendicular wall shall be provided with wall mounted stop:
      1. Ives WS406/407
      2. Rockwood 406/409
      3. Trimco 1270WV/WX
      This is the preferred door stop application.
    2. Where required, floor mounted stop to be:
      1. Rockwood 442
      2. Ives FS438
      3. Trimco W1211
    3. Where neither floor or wall stops are applicable, provide overhead track stop:
      1. Surface mount heavy duty:
        1. Glynn Johnson 90
        2. Rixson 9-x36
        3. Sargent 590
      2. Surface mount standard duty:
        1. Glynn Johnson 450
        2. Rixson 10-x36
        3. Sargent 1540
        4. (use at closets and low-use doors)
      3. Concealed mount heavy duty:
        1. Glynn Johnson 100
        2. Rixson 1-x36
        3. Sargent 690
        4. (use at doors with Parallel Arm push side door closers)
    4. Do not specify automatic holders at exterior doors.
  8. Finishes:
    1. Standard finishes as follows:
      1. Interior hinges, locks, floor stops: US26D/652 Satin Chrome.
      2. Exterior hinges, push-pulls, kickplates, exit devices: US32D/630 stainless steel.
      3. Doors closers and accessories: 689 / AL powder coat aluminum finish.
      4. Other finishes may be warranted to match existing and need prior approval.
  9. Miscellaneous Requirements:
    1. SUBSTITUTIONS: This standard allows for three (3) solutions from unique corporations for all major items (hinges, locksets, exit devices, door closers and cylinders). In order to maintain quality on the campus, the University will not accept any alternates or substitutions to these items as specified above, unless prior written approval from Office of Physical Plant (OPP) is granted.
    2. Doors with push-pulls in conjunction with a cylinder deadlock will be drilled for cylinders.
    3. Provide rubber silencers at all hollow metal frames that do NOT receive sound seal or smoke gasket: Rockwood 608 or Ives 20.
    4. If required, any padlock supplied to be small-format 7-pin key system to match existing.
    5. Furnish padlocks for all transformer gates.
    6. Provide kickplates at any door scheduled with a door closer.
    7. Wood doors that are schedule with door closers to have sufficient blocking built in to meet a 1,000,000 slam cycle test. Thru-bolting of door closers is not acceptable.
    8. Flush bolts should be installed in edge of door.
    9. All push plates should be 8" x 16" unless not possible because of size constraints.
    10. All hardware to be installed according to manufacturer's recommendations unless specified for an atypical installation.