13 21 00 RADIOISOTOPE LABORATORY DESIGN
- Former user (Deleted)
Owned by Former user (Deleted)
Aug 01, 2017
Loading data...
.01 General
- A laboratory designed for the use of chemicals is suitable for most of the experiments at a university using radioactive material. Benchtops, shelving and sinks should have smooth impervious surfaces with a minimum of joints. Stainless steel is very suitable and may be required where chemicals are used that dissolve or react with organic coatings. Soapstone, wood, and other porous material should not be used. However, trays and absorbent paper are recommended when using any quantity of radioactive material making it possible to work with even these poor surfaces.
.02 Floors
- Floors should also be impervious. Tile floors have joints that can collect contamination but have the advantage that contaminated sections can be easily removed and replaced. Epoxy finishes can also be provided that are smooth, impervious, long-wearing and repairable.
.03 Eating Area
- One item that is often overlooked is the need for an eating area separate from the laboratory. In radioisotope laboratories food storage, food preparation, and eating or drinking are prohibited. Therefore, refrigerators and sinks in laboratories may not be used for storage, refrigeration of food, or washing eating utensils. The eating area must be an area separate from the laboratory; either a separate room or a partition from the rest of the laboratory. If offices are to be used for eating areas, sinks should be provided for food preparation. The study cubicles used inside some laboratories do not meet the requirements for a separate eating area.
.04 Sinks
- Sink drains may be of any material compatible with the chemicals to be used. Sink traps should be readily removable for recovery of lost items and contamination checks. Glass plumbing should be protected against heavy objects, such as magnetic stirrers, that can fall through large distances in vertical pipes and break the glass pipe. Glass drain should also be protected from freezing and routed so that leakage goes into pipe chases and not through ceilings into laboratories and offices.
.05 Fume Hoods
- It is the general policy at the University that radioisotope experiments be designed so that a hood is not needed to meet the requirements for concentration of airborne radioactive material. Hoods serve only as a backup in case of unanticipated release of radioactive material. Therefore, well designed chemical hoods are suitable for most radioisotope work.
- Hoods should be designed for a face velocity of about 100 feet per minute. Some hoods with separate makeup air systems may not meet the face velocity requirement but still give satisfactory performance if the collection efficiency for airborne material released in the hood is equivalent to that of a 100 fpm face velocity.
- Hoods should be located away from doors, windows, heavy traffic areas and other sources of drafts that could cause backflow from the hood.
- Sufficient makeup air is to be provided to the hood or room to allow for proper air flow. Blowers should be located as close to the exhaust end of the ducting as practicable. Duct velocity should be as high as possible to reduce duct contamination without creating a noise problem or requiring excessive energy to operate at a high pressure drop.
- One exception to the above hood requirement is the design of hoods for radioiodination. Such hoods must meet the following additional requirements:
- A minimal linear face velocity of 100 fpm minimum.
- An activated carbon filter for radioiodine plus a prefilter to reduce dust loading of the activated carbon. The activated carbon filter should be designed for a minimum contact time of 0.25 second. Filters are to be of standard AEC design (24" x 24" cross-section, up to 12" deep) and interchangeable with HEPA filters.
- Stainless steel interior for ease of decontamination.
- A mercury-free manometer to indicate filter pressure drop mounted at the hood face.
- A low-flowrate alarm. A direct reading manometer with pressure switches such as the Dwyer Photohelic gauge can serve as the manometer and flow-rate alarm.
.06 Animal Rooms
- Rooms that meet the requirements for animal care can usually be used for in-vivo radioisotope experiments. The room should be large enough to accommodate extra waste containers and monitoring equipment during an experiment, typically about 25-50 square feet. If the experiment involves larger numbers of small animals or large animals it may be necessary to use anticontamination clothing and additional space for a change pad and clothing storage (50-100 square feet) is needed.
- Walls and floors of animal rooms should be easily cleaned. A bare room with tile or epoxy floor and walls is recommended.
- Furniture should be movable or easily washed in place.
- At least one large, deep-bowl sink, preferably of stainless steel should be provided.
- AÂ hose bib with hot and cold mixing faucet is recommended for washing floor and walls.
.07 Miscellaneous
- There should be sufficient walk in freezer space (20-40 square feet) available for extended storage of contaminated animal carcasses for radioactive decay. Laboratory space adjacent to the animal room is recommended for preparation of radiochemicals, and processing of samples. At least one table of sufficient size to handle the largest animal expected to be used should be provided for surgical procedures, implanting catheters, drawing blood samples, etc.
- Each radioisotope laboratory should have at least one cabinet that can be locked for storage of radioisotopes. If refrigerated storage of radiochemicals is required, a refrigerator or freezer with a lock is required.
- Specialized laboratories for the use of alpha-emitting radionuclides and high intensity gamma ray sources may require additional features such as a change area for work clothes, filtration of exhaust air and shielded storage space for radioisotopes.