23 50 00 CENTRAL HEATING EQUIPMENT
- Former user (Deleted)
Owned by Former user (Deleted)
Aug 01, 2017
1 min read
Loading data...
.01 Combustion Safeguards
- All fuel burner combustion safeguards on gas-fired boilers over 100 HP and oil-fired boilers over 50 HP should be Factory Mutual approved equipment.
- Drawings, including section details of wiring and gas train, along with a Factory Mutual Application for acceptance form, shall be submitted to Factory Mutual for review and acceptance prior to installation.
- Final approval is based on a satisfactory field test of completed installation.
- Gas fired unit heaters up to 400,000 BTUs need AGA approval.
Page Navigation
Related Files
File | Modified |
---|