21 09 00 INSTRUMENTATION AND CONTROL FOR FIRE-SUPPRESSION SYSTEMS
.01 Building Fire Alarm Panel
The building fire alarm panel described in Division 28 shall receive signals from fire pumps (pump running, phase reversal, pump trouble, and loss of power), water-flow alarm devices, alarm valves, CO2 systems, Halon systems, tamper switches, and others as required for the project.
At a minimum, signals shall be alarm, trouble, and supervisory conditions.